CU/PVC/STA/PVC, AL/PVC/STA/PVC 0.6/1kV
Constructions
Conductor: Plain circular stranded copper/aluminum conductor, conform to IEC 60228 class 2
Insulation: PVC/A
Inner Covering: PVC
Armoring: Steel Tape
Sheath: PVC type ST2 to IEC 60502, black
Note: Insulation color as per standards or at request
Applications
Suitable for use in power distribution lines or fixed installations with rated voltage up to 0.6/1 kV. Suitable for burying in ground, Able to bear external mechanical forces but large pulling forces.
Standards
International: IEC 60502, IEC 60228
China: GB/T 12706.1-2008
Other standards such as BS,DIN and ICEA upon request
Technical data
Rated voltage: 0.6 / 1 kV
Max. Conductor Temp.: normal (70℃), short circuit no more than 5 s (160℃ when section-area below 300mm2, 140℃ when section-area above 300mm2)
Min. Ambient Temp.: 0℃, after installation and only when cable is in a fixed position
Min. Bending Radius: 15 x cable O.D for single-core armored cables
12 x cable O.D for multi-core armored cables
Certificates
CE, RoHS, CCC, KEMA and more others at request
Model No. |
Construction |
Applications |
VV22 |
PVC Insulated,Steel Tape Armored,PVC Sheathed Power Cable |
Suitable for burying in ground, Able to bear external mechanical forces but large pulling forces. |
VLV22 |
Al. Insulated,Steel Tape Armored,PVC Sheathed Power Cable |