Constructions
Conductor: Plain circular stranded copper conductor, conform to IEC 60228 class 2
Insulation: PVC/A
Binder: Non-woven
Sheath: PVC type ST2 to IEC 60502, black
Fillers: Paper
Note: Insulation color as per standards or at request
Applications
Suitable for use in power distribution lines or fixed installations with rated voltage up to 0.6/1 kV indoor/outdoor, enclosed in conduit, in underground duct where not subject to mechanical damage.
Standards
International: IEC 60502, IEC 60228
China: GB/T 12706.1-2008
Other standards such as BS,DIN and ICEA upon request
Technical data
Rated voltage: 0.6 / 1 kV
Max. Conductor Temp.: normal (70℃), short circuit no more than 5 s (160℃ when section-area below 300mm2, 140℃ when section-area above 300mm2)
Min. Ambient Temp.: 0℃, after installation and only when cable is in a fixed position
Min. Bending Radius: 20 x cable O.D
Certificates
CE, RoHS, CCC, KEMA and more others at request
Model No. |
Construction |
Applications |
VV |
Copper Conductor, PVC Insulated, PVC Sheathed Power Cable |
For laying indoors and outdoors. Able to bear certain traction during installation, but not external mechanical forces. Laying single core cable in magnetic ducts is not allowed. |