CONDUCTORS
Stranded bare copper conductors
CEI 20-29 cl.5, EN 60228, IEC 60228 ref.
|
INSULATION
Special halogen free low smoke compound
Colour code: differently coloured
|
SHIELD (OPTIONAL)
Aluminium/polyester tape helically wound with
stranded bare copper drain wire
|
JACKET
Special halogen free low smoke compound
CEI 20-11 quality M1, VDE 0207 HM2
colour: White or on request
|
ELECTRICAL CONDUCTOR RESISTANCE
0,22 mm2: < 89 Ohm/Km
0,50 mm2: < 39 Ohm/Km
0,75 mm2: < 26 Ohm/Km
1,00 mm2: < 19,5 Ohm/Km
1,50 mm2: < 13,5 Ohm/Km
2,50 mm2: < 7,9 Ohm/Km
|
WORKING TEMPERATURE
-20°C + 80°C
|
BENDING RADIUS
15 times overall diameter of cable
|
WORKING VOLTAGE
50 V max
|
TEST VOLTAGE
2000 V
|
FLAME RETARDANT TEST
CEI 20-35/1-2, EN 60332-2-1, CEI 20-22/3-4,
EN 60332-3-24, IEC 60332-3-24
|
NON-HALOGEN VERIFICATION
0,5 % (CEI 20-37/2-1, CEI EN 50267-2-1, IEC 60754-1)
CORROSIVITY OF COMBUSTION GASES
Ph: > 4,3 Conductivity: < 10 Μs/mm (CEI 20-37/2-2, CEI EN 50267-2-2, IEC 60754-2)
SMOKE DENSITY
Transmission of light: > 60% (CEI 20-37/3-1)
TOXICITY INDEX
< 2 (CEI 20-37/7)
|
|
|